The Intevio series features a powerful dual-channel audio matrix, up to 128 loudspeaker lines plus a high-speed data bus for unmatched sound reproduction in public settings. Other world-class features include digital volume control, comprehensive supervision, hot standby and easy integration with fire alarm panels
The HCU-2000 controller is the core unit of Honeywell’s Intevio PAVA systems. It effortlessly performs multiple critical functions like audio storage and playback, signal processing, zone control, routing, scheduled broadcasts, supervision and fault detection. It meets international standards for safety. With its built-in 500W Class-D amplifier, this single controller can work as an integrated, 8-zone PAVA system for better stability, cost savings and superb user experience.
Model No. | HCU-2000 |
---|---|
Main Power Supply Voltage | AC 220-240V, 50/60Hz |
Rated Power | 750W |
Gross Weight | 17.4Kg |
Backup power supply | AC 220-240V, 50/60Hz |
Main Power Supply Fuse | T10AH 250V |
Microphone Input Sensitivity | -65±3dBV |
Microphone Input Impedance | 250Ω |
Microphone Input Frequency Response | 90 Hz -13KHz |
Microphone Input SNR | >50dB (with A-Weight) |
Auxiliary input Input channels | 2 |
Auxiliary Input Sensitivity | 1V (0dBV) |
Auxiliary input Input impedance | 10 KΩ |
Auxiliary input Frequency response | 85Hz-18KHz |
Auxiliary Input SNR | >77dB (with A-Weight) |
Mic/Line Input Sensitivity | -50dBV/0dBV, selectable |
Mic/Line Input Impedance | 10 KΩ |
Mic/Line Input Frequency Response | 85Hz-18KHz |
Mic/Line Input SNR | >77dB (with A-Weight) |
Mic/Line Input Phantom Power | DC 24V, switchable |
Call Station Interface Input Signal | 2V |
Call Station Interface Input Impedance | 20 KΩ |
Call Station Interface Output Signal | 2V |
Call Station Interface Output Impedance | 20 KΩ |
Call Station Interface Frequency Response | 85Hz-18KHz |
Audio Output Channels | Channel 1, channel 2 and recording output |
Audio Output signal | 1V (0dBV) |
Audio Output THD | <0.5% |
Amplifier Control Interfaces Channels | 3 (channel 1, channel 2 and backup amplifier) |
Amplifier Control Interfaces Output Signal | 1.4V |
Amplifier Control Interfaces THD | <0.5% |
Amplifier Control Interfaces Control Signal | Self-test signal, amplifier fault signal and power saving control signal |
Loudspeaker Circuits Output Channels | 8 (with group A and group B) |
Loudspeaker Circuits Load | 500W |
Contact Inputs | 10 (monitored) |
Contact Outputs | 8 (NO, NC & COM), “fault output, emergency output |
MAX. Working Voltage for Outputs | AC 250V/DC 30V |
MAX. Working current for Outputs | 2.5A |
DC power output | 24V/1A |
Ethernet Port | 10M/100M |
Memory Capacity | 1GB |
Humidity | < 95%, without condensation |
Operating Temperature | -10°C~+50°C (14°F~+122°F) |
Storage Temperature | -40°C~+70°C (-40°F~+158°F) |
Product dimensions (W×H×D) | 482 mm×133.5 mm×420 mm |
Package dimension (W×H×D) | 580 mm×279 mm×552 mm |
Net Weight | 14.3Kg |
abc | 24V/1A |
Monitoring Loudspeaker | 2W/8Ω |
Model No. | HCU-2000 |
---|---|
Description | Controller |
Documentation | Size | Release Date | File Type | Download |
---|---|---|---|---|
Datasheet | 2465.96 KB | 07.11.2020 | Download | |
With our innovative approach in product design and advanced production technical capabilities for building environments of any size