The IQECO31 is a terminal unit controller for use with BACnet over MS/TP. It can communicate with other IQECOs over the BACnet MS/TP network, and with Trend networked devices by using an IQ4NC. It has 10 I/O channels and can be supplied as a fixed or programmable unit, with Trend written strategies, custom strategies or no strategy.
The IQECO can be purchased either as a fully programmable or a fixed strategy model. A wide range of strategies can be downloaded to the units to provide pre-configured functionality for a host of different applications. They are classified as Entry level (E), Basic (B) or Plus (P)and can be downloaded into the respective controllers. The more popular application strategies can be ordered directly from the factory. Please see price list for details. The fixed strategy controllers will allow a degree of configuration while the programmable models allow complete flexibility. Should it be necessary to upgrade from a fixed to programmable an unlock is available.
• The programmable units allow the strategy to be modified to meet specific project requirements whereas the fixed units can only be used with a Trend supplied strategy.
• The strategy itself defines the units HVAC control method. Various Trend strategies are available and they are divided into three categories, Entry, Basic and Plus. The Entry category has less sophisticated strategies with a lower level of I/O control and the Plus category has more sophisticated strategies with the highest level of I/O control.
• Trend provide a service to supply personal strategies preloaded into the IQECO. This can significantly reduce time on site by removing the need to download the same strategy to potentially several hundred controllers.
• Units defined as No Strategy are supplied empty and can have strategies downloaded from SET.
UI | 1 |
DI | 1 |
TI | 2 |
AO | 1 |
DO | 4 |
Relay outputs | 1 |
Power supply | 24 Vac |
|
||||
Description | Additional Product Type | Downloads | ||
---|---|---|---|---|
TXT | ||||
Web enabled controller with no I/O points, non expandable by the I/O bus. Provides routing between MS/TP BACnet, Ethernet and Trend LAN. 100 to 240 Vac. | IQ4NC/00/230 |
|
||
Specification sheet (French) |
||||
Web enabled controller with no I/O points, non expandable by the I/O bus. Provides routing between MS/TP BACnet, Ethernet and Trend LAN. 24 Vac or 24 to 36 Vdc. | IQ4NC/00/24VAC |
|
||
Specification sheet (French) |
||||
Web enabled controller with 12 I/O points, non expandable by the I/O bus. Provides routing between MS/TP BACnet, Ethernet and Trend LAN. 100 to 240 Vac. | IQ4NC/12/230 |
|
||
Specification sheet (French) |
||||
Web enabled controller with 12 I/O points, non expandable by the I/O bus. Provides routing between MS/TP BACnet, Ethernet and Trend LAN. 24 Vac or 24 to 36 Vdc. | IQ4NC/12/24VAC |
|
||
Specification sheet (French) |
||||
Screened twisted-pair cable for MSTP network 24 AWG 305 metre. | TP/1/1/24/HF/305/600V |
|
||
Specification sheet (English) |
||||
Upgrade licence to convert a fixed strategy controller to a programmable controller. | IQE/PROG/UP |
|
— | |
Room Displays for use with IQECO controller. | RD-WMB-T |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Displays for use with IQECO controller. | RD-WMB-TH |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Displays for use with IQECO controller. | RD-WMB-TC |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Displays for use with IQECO controller. | RD-WMB-THC |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Sensors for use with IQECO controller. | RS-WMB-T |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Sensors for use with IQECO controller. | RS-WMB-TC |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Sensors for use with IQECO controller. | RS-WMB-TH |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Sensors for use with IQECO controller. | RS-WMB-THC |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Wall mounting thermistor space temperature sensor. | TB/TS |
|
||
Specification sheet (English) Installation/startup instruction (English) |
||||
As TB/TS plus setpoint adjustment. | TB/TS/K |
|
||
Specification sheet (English) |
||||
IQECO/IQL secondary terminal cover. | ENCLS-600002 |
|
||
Specification sheet (English) |
The IQECO31 is a terminal unit controller for use with BACnet over MS/TP. It can communicate with other IQECOs over the BACnet MS/TP network, and with Trend networked devices by using an IQ4NC. It has 10 I/O channels and can be supplied as a fixed or programmable unit, with Trend written strategies, custom strategies or no strategy.
The IQECO can be purchased either as a fully programmable or a fixed strategy model. A wide range of strategies can be downloaded to the units to provide pre-configured functionality for a host of different applications. They are classified as Entry level (E), Basic (B) or Plus (P)and can be downloaded into the respective controllers. The more popular application strategies can be ordered directly from the factory. Please see price list for details. The fixed strategy controllers will allow a degree of configuration while the programmable models allow complete flexibility. Should it be necessary to upgrade from a fixed to programmable an unlock is available.
• The programmable units allow the strategy to be modified to meet specific project requirements whereas the fixed units can only be used with a Trend supplied strategy.
• The strategy itself defines the units HVAC control method. Various Trend strategies are available and they are divided into three categories, Entry, Basic and Plus. The Entry category has less sophisticated strategies with a lower level of I/O control and the Plus category has more sophisticated strategies with the highest level of I/O control.
• Trend provide a service to supply personal strategies preloaded into the IQECO. This can significantly reduce time on site by removing the need to download the same strategy to potentially several hundred controllers.
• Units defined as No Strategy are supplied empty and can have strategies downloaded from SET.
UI | 1 |
DI | 1 |
TI | 2 |
AO | 1 |
DO | 4 |
Relay outputs | 1 |
Power supply | 230 Vac |
|
||||||
Application | Control | Programability | Type | Downloads | ||
---|---|---|---|---|---|---|
TXT | ||||||
1 speed fan | Air/Raise/Lower/Damper: (AR2) | Fixed | IQE31/F/BAC/1SFANAR2B/230 |
|
||
Specification sheet (English) Application manual (English) Installation/mounting instruction (English) |
||||||
1 speed fan | Water/Raise/Lower/2 pipe | Fixed | IQE31/F/BAC/1SFANWR2B/230 |
|
||
Specification sheet (English) Application manual (English) Installation/mounting instruction (English) |
||||||
1 speed fan | Water/Thermic/4 pipe | Fixed | IQE31/F/BAC/1SFANWT4B/230 |
|
||
Specification sheet (English) Application manual (English) Installation/mounting instruction (English) |
||||||
EC fan | Water/Raise/Lower/2 pipe | Fixed | IQE31/F/BAC/ECFANWR2P/230 |
|
||
Specification sheet (English) Application manual (English) Installation/mounting instruction (English) |
||||||
EC fan | Water/Raise/Lower/4 pipe | Fixed | IQE31/F/BAC/ECFANWR4P/230 |
|
||
Specification sheet (English) Application manual (English) Installation/mounting instruction (English) |
||||||
EC fan | Water/Thermic/2 pipe | Fixed | IQE31/F/BAC/ECFANWT2P/230 |
|
||
Specification sheet (English) Application manual (English) Installation/mounting instruction (English) |
||||||
EC fan | Water/Thermic/4 pipe | Fixed | IQE31/F/BAC/ECFANWT4P/230 |
|
||
Specification sheet (English) Application manual (English) Installation/mounting instruction (English) |
||||||
— | No strategy | Fixed | IQE31/F/BAC/NOSTRATEGY/230 |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||||
1 speed fan | Air/Raise/Lower/Damper: (AR2) | Programmable | IQE31/P/BAC/1SFANAR2B/230 |
|
||
Specification sheet (English) Application manual (English) Installation/mounting instruction (English) |
||||||
1 speed fan | Water/Raise/Lower/2 pipe | Programmable | IQE31/P/BAC/1SFANWR2B/230 |
|
||
Specification sheet (English) Application manual (English) Installation/mounting instruction (English) |
||||||
1 speed fan | Water/Raise/Lower/4 pipe | Programmable | IQE31/P/BAC/1SFANWR4B/230 |
|
||
Specification sheet (English) Application manual (English) Installation/mounting instruction (English) |
||||||
1 speed fan | Water/Thermic/4 pipe | Programmable | IQE31/P/BAC/1SFANWT4B/230 |
|
||
Specification sheet (English) Application manual (English) Installation/mounting instruction (English) |
||||||
EC fan | Water/Raise/Lower/2 pipe | Programmable | IQE31/P/BAC/ECFANWR2P/230 |
|
||
Specification sheet (English) Application manual (English) Installation/mounting instruction (English) |
||||||
EC fan | Water/Raise/Lower/4 pipe | Programmable | IQE31/P/BAC/ECFANWR4P/230 |
|
||
Specification sheet (English) Application manual (English) Installation/mounting instruction (English) |
||||||
EC fan | Water/Thermic/2 pipe | Programmable | IQE31/P/BAC/ECFANWT2P/230 |
|
||
Specification sheet (English) Application manual (English) Installation/mounting instruction (English) |
||||||
EC fan | Water/Thermic/4 pipe | Programmable | IQE31/P/BAC/ECFANWT4P/230 |
|
||
Specification sheet (English) Application manual (English) Installation/mounting instruction (English) |
||||||
— | No strategy | Programmable | IQE31/P/BAC/NOSTRATEGY/230 |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||||
— | Custom strategy | Custom | IQE31/C/BAC/Custom/230 |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
|
||||
Description | Additional Product Type | Downloads | ||
---|---|---|---|---|
TXT | ||||
Web enabled controller with no I/O points, non expandable by the I/O bus. Provides routing between MS/TP BACnet, Ethernet and Trend LAN. 100 to 240 Vac. | IQ4NC/00/230 |
|
||
Specification sheet (English) |
||||
Web enabled controller with no I/O points, non expandable by the I/O bus. Provides routing between MS/TP BACnet, Ethernet and Trend LAN. 24 Vac or 24 to 36 Vdc. | IQ4NC/00/24VAC |
|
||
Specification sheet (English) |
||||
Web enabled controller with 12 I/O points, non expandable by the I/O bus. Provides routing between MS/TP BACnet, Ethernet and Trend LAN. 100 to 240 Vac. | IQ4NC/12/230 |
|
||
Specification sheet (English) |
||||
Web enabled controller with 12 I/O points, non expandable by the I/O bus. Provides routing between MS/TP BACnet, Ethernet and Trend LAN. 24 Vac or 24 to 36 Vdc. | IQ4NC/12/24VAC |
|
||
Specification sheet (English) |
||||
Screened twisted-pair cable for MSTP network 24 AWG 305 metre. | TP/1/1/24/HF/305/600V |
|
||
Specification sheet (English) |
||||
Upgrade licence to convert a fixed strategy controller to a programmable controller. | IQE/PROG/UP |
|
— | |
Room Display for use with IQECO controller. | RD-WMB-T |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Display for use with IQECO controller. | RD-WMB-TH |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Display for use with IQECO controller. | RD-WMB-TC |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Display for use with IQECO controller. | RD-WMB-THC |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Sensor for use with IQECO controller. | RS-WMB-T |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Sensor for use with IQECO controller. | RS-WMB-TH |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Sensors for use with IQECO controller. | RS-WMB-TC |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Sensors for use with IQECO controller. | RS-WMB-THC |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Wall mounting thermistor space temperature sensor. | TB/TS |
|
||
Specification sheet (English) Installation/startup instruction (English) |
||||
As TB/TS plus setpoint adjustment. | TB/TS/K |
|
||
Specification sheet (English) |
||||
IQECO/IQL secondary terminal cover. | ENCLS-600002 |
|
||
Specification sheet (English) |
The IQECO32 is a terminal unit controller for use with BACnet over MS/TP. It can communicate with other IQECOs over the BACnet MS/TP network, and with Trend networked devices via an IQ4NC. It has 9 I/O channels and can be supplied with custom strategies or as a programmable unit with no strategy.
Programmable: This IQECO version is fully programmable using IQ SET. This programmable controller will be supplied with no strategy. The standard strategies are available in IQ SET as solutions and can be downloaded directly or modified as required in the normal way.
• Custom: The IQECO can be supplied with a strategy written by the customer. Trend will supply the strategy already downloaded into a programmable IQECO saving time on site. For this option the customer strategy must be supplied with the order; Trend will not test the strategy it will only ensure that the strategy supplied with the order can be successfully loaded into a controller.
UI | 1 |
DI | 1 |
TI | 2 |
AO | 4 |
DO | 0 |
Relay outputs | 1 |
Power supply | 24 Vac |
|
|||||
Control | Programability | Type | Downloads | ||
---|---|---|---|---|---|
TXT | |||||
No strategy | Programmable | IQE32/P/BAC/NOSTRATEGY/24VAC |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
|||||
Custom strategy | Custom | IQE32/C/BAC/Custom/24VAC |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
|
||||
Description | Additional Product Type | Downloads | ||
---|---|---|---|---|
TXT | ||||
Web enabled controller with no I/O points, non expandable by the I/O bus. Provides routing between MS/TP BACnet, Ethernet and Trend LAN. 100 to 240 Vac. | IQ4NC/00/230 |
|
||
Specification sheet (English) |
||||
Web enabled controller with no I/O points, non expandable by the I/O bus. Provides routing between MS/TP BACnet, Ethernet and Trend LAN. 24 Vac or 24 to 36 Vdc. | IQ4NC/00/24VAC |
|
||
Specification sheet (English) |
||||
Web enabled controller with 12 I/O points, non expandable by the I/O bus. Provides routing between MS/TP BACnet, Ethernet and Trend LAN. 100 to 240 Vac. | IQ4NC/12/230 |
|
||
Specification sheet (English) |
||||
Web enabled controller with 12 I/O points, non expandable by the I/O bus. Provides routing between MS/TP BACnet, Ethernet and Trend LAN. 24 Vac or 24 to 36 Vdc. | IQ4NC/12/24VAC |
|
||
Specification sheet (English) |
||||
Screened twisted-pair cable for MSTP network 24 AWG 305 metre. | TP/1/1/24/HF/305/600V |
|
||
Specification sheet (English) |
||||
Upgrade licence to convert a fixed strategy controller to a programmable controller. | IQE/PROG/UP |
|
— | |
Room Displays for use with IQECO controller. | RD-WMB-T |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Displays for use with IQECO controller. | RD-WMB-TH |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Displays for use with IQECO controller. | RD-WMB-TC |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Displays for use with IQECO controller. | RD-WMB-THC |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Sensors for use with IQECO controller. | RS-WMB-T |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Sensors for use with IQECO controller. | RS-WMB-TC |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Sensors for use with IQECO controller. | RS-WMB-TH |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Sensors for use with IQECO controller. | RS-WMB-THC |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Wall mounting thermistor space temperature sensor. | TB/TS |
|
||
Specification sheet (English) Installation/startup instruction (English) |
||||
As TB/TS plus setpoint adjustment. | TB/TS/K |
|
||
Specification sheet (English) |
||||
IQECO/IQL secondary terminal cover. | ENCLS-600002 |
|
||
Specification sheet (English) |
The IQECO32 is a terminal unit controller for use with BACnet over MS/TP. It can communicate with other IQECOs over the BACnet MS/TP network, and with Trend networked devices via an IQ4NC. It has 9 I/O channels and can be supplied with custom strategies or as a programmable unit with no strategy.
Programmable: This IQECO version is fully programmable using IQ SET. This programmable controller will be supplied with no strategy. The standard strategies are available in IQ SET as solutions and can be downloaded directly or modified as required in the normal way.
• Custom: The IQECO can be supplied with a strategy written by the customer. Trend will supply the strategy already downloaded into a programmable IQECO saving time on site. For this option the customer strategy must be supplied with the order; Trend will not test the strategy it will only ensure that the strategy supplied with the order can be successfully loaded into a controller.
UI | 1 |
DI | 1 |
TI | 2 |
AO | 4 |
DO | 0 |
Relay outputs | 1 |
Auxiliary output signal | 24 Vdc |
Power supply | 230 Vac |
|
|||||
Control | Programability | Type | Downloads | ||
---|---|---|---|---|---|
TXT | |||||
No strategy | Programmable | IQE32/P/BAC/NOSTRATEGY/230 |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
|||||
Custom strategy | Custom | IQE32/C/BAC/Custom/230 |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
|
||||
Description | Additional Product Type | Downloads | ||
---|---|---|---|---|
TXT | ||||
Web enabled controller with no I/O points, non expandable by the I/O bus. Provides routing between MS/TP BACnet, Ethernet and Trend LAN. 100 to 240 Vac. | IQ4NC/00/230 |
|
||
Specification sheet (English) |
||||
Web enabled controller with no I/O points, non expandable by the I/O bus. Provides routing between MS/TP BACnet, Ethernet and Trend LAN. 24 Vac or 24 to 36 Vdc. | IQ4NC/00/24VAC |
|
||
Specification sheet (English) |
||||
Web enabled controller with 12 I/O points, non expandable by the I/O bus. Provides routing between MS/TP BACnet, Ethernet and Trend LAN. 100 to 240 Vac. | IQ4NC/12/230 |
|
||
Specification sheet (English) |
||||
Web enabled controller with 12 I/O points, non expandable by the I/O bus. Provides routing between MS/TP BACnet, Ethernet and Trend LAN. 24 Vac or 24 to 36 Vdc. | IQ4NC/12/24VAC |
|
||
Specification sheet (English) |
||||
Screened twisted-pair cable for MSTP network 24 AWG 305 metre. | TP/1/1/24/HF/305/600V |
|
||
Specification sheet (English) |
||||
Upgrade licence to convert a fixed strategy controller to a programmable controller. | IQE/PROG/UP |
|
— | |
Room Display for use with IQECO controller. | RD-WMB-T |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Display for use with IQECO controller. | RD-WMB-TH |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Display for use with IQECO controller. | RD-WMB-TC |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Display for use with IQECO controller. | RD-WMB-THC |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Sensor for use with IQECO controller. | RS-WMB-T |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Sensor for use with IQECO controller. | RS-WMB-TH |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Sensors for use with IQECO controller. | RS-WMB-TC |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Sensors for use with IQECO controller. | RS-WMB-THC |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Wall mounting thermistor space temperature sensor. | TB/TS |
|
||
Specification sheet (English) Installation/startup instruction (English) |
||||
As TB/TS plus setpoint adjustment. | TB/TS/K |
|
||
Specification sheet (English) |
||||
IQECO/IQL secondary terminal cover. | ENCLS-600002 |
|
||
Specification sheet (English) |
The IQECO35 is a terminal unit controller for use with BACnet over MS/TP. It can communicate with other IQECOs over the BACnet MS/TP network, and with Trend networked devices by using an IQ4NC. It has 17 I/O channels, and can be supplied as a fixed or programmable unit, with Trend written strategies, custom strategies or no strategy.
The IQECO can be purchased either as a fully programmable or a fixed strategy model. A wide range of strategies can be downloaded to the units to provide pre-configured functionality for a host of different applications. They are classified as Entry level (E), Basic (B) or Plus (P)and can be downloaded into the respective controllers. The more popular application strategies can be ordered directly from the factory. Please see price list for details. The fixed strategy controllers will allow a degree of configuration while the programmable models allow complete flexibility. Should it be necessary to upgrade from a fixed to programmable an unlock is available.
• The programmable units allow the strategy to be modified to meet specific project requirements whereas the fixed units can only be used with a Trend supplied strategy.
• The strategy itself defines the units HVAC control method. Various Trend strategies are available and they are divided into three categories, Entry, Basic and Plus. The Entry category has less sophisticated strategies with a lower level of I/O control and the Plus category has more sophisticated strategies with the highest level of I/O control.
• Trend provide a service to supply personal strategies preloaded into the IQECO. This can significantly reduce time on site by removing the need to download the same strategy to potentially several hundred controllers.
• Units defined as No Strategy are supplied empty and can have strategies downloaded from SET.
UI | 3 |
DI | 2 |
TI | 3 |
AO | 1 |
DO | 4 |
Relay outputs | 4 |
Auxiliary output signal | 1 x 24 Vdc |
Power supply | 24 Vac |
|
|||||||
Application | Control | Programability | Additional functions | Type | Downloads | ||
---|---|---|---|---|---|---|---|
TXT | |||||||
3 speed fan | Water/Raise/Lower/2 pipe | Fixed | — | IQE35/F/BAC/3SFANWR2E/24VAC |
|
||
Specification sheet (English) Application manual (English) Installation/mounting instruction (English) |
|||||||
3 speed fan | Water/Raise/Lower/4 pipe | Fixed | — | IQE35/F/BAC/3SFANWR4E/24VAC |
|
||
Specification sheet (English) Application manual (English) Installation/mounting instruction (English) |
|||||||
3 speed fan | Water/Raise/Lower/4 pipe | Fixed | Electrical heat at 1% demand | IQE35/F/BAC/3SFANWR4EB/24VAC |
|
||
Specification sheet (English) Application manual (English) Installation/mounting instruction (English) |
|||||||
3 speed fan | Water/Thermic/4 pipe | Fixed | — | IQE35/F/BAC/3SFANWT4E/24VAC |
|
||
Specification sheet (English) Application manual (English) Installation/mounting instruction (English) |
|||||||
3 speed fan | Water/Raise/Lower/2 pipe | Programmable | — | IQE35/P/BAC/3SFANWR2E/24VAC |
|
||
Specification sheet (English) Application manual (English) Installation/mounting instruction (English) |
|||||||
3 speed fan | Water/Raise/Lower/4 pipe | Programmable | — | IQE35/P/BAC/3SFANWR4E/24VAC |
|
||
Specification sheet (English) Application manual (English) Installation/mounting instruction (English) |
|||||||
3 speed fan | Water/Raise/Lower/4 pipe | Programmable | Electrical heat at 1% demand | IQE35/P/BAC/3SFANWR4EB/24VAC |
|
||
Specification sheet (English) Application manual (English) Installation/mounting instruction (English) |
|||||||
3 speed fan | Water/Thermic/4 pipe | Programmable | — | IQE35/P/BAC/3SFANWT4E/24VAC |
|
||
Specification sheet (English) Application manual (English) Installation/mounting instruction (English) |
|||||||
— | Custom strategy | Fixed | — | IQE35/C/BAC/CUSTOM/24VAC |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
|||||||
— | No strategy | Fixed | — | IQE35/F/BAC/NOSTRATEGY/24VAC |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
|||||||
— | No strategy | Programmable | — | IQE35/P/BAC/NOSTRATEGY/24VAC |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
|
||||
Description | Additional Product Type | Downloads | ||
---|---|---|---|---|
TXT | ||||
Web enabled controller with no I/O points, non expandable by the I/O bus. Provides routing between MS/TP BACnet, Ethernet and Trend LAN. 100 to 240 Vac. | IQ4NC/00/230 |
|
||
Specification sheet (English) |
||||
Web enabled controller with no I/O points, non expandable by the I/O bus. Provides routing between MS/TP BACnet, Ethernet and Trend LAN. 24 Vac or 24 to 36 Vdc. | IQ4NC/00/24VAC |
|
||
Specification sheet (English) |
||||
Web enabled controller with 12 I/O points, non expandable by the I/O bus. Provides routing between MS/TP BACnet, Ethernet and Trend LAN. 100 to 240 Vac. | IQ4NC/12/230 |
|
||
Specification sheet (English) |
||||
Web enabled controller with 12 I/O points, non expandable by the I/O bus. Provides routing between MS/TP BACnet, Ethernet and Trend LAN. 24 Vac or 24 to 36 Vdc. | IQ4NC/12/24VAC |
|
||
Specification sheet (English) |
||||
Screened twisted-pair cable for MSTP network 24 AWG 305 metre. | TP/1/1/24/HF/305/600V |
|
||
Specification sheet (English) |
||||
Upgrade licence to convert a fixed strategy controller to a programmable controller. | IQE/PROG/UP |
|
— | |
Room Display for use with IQECO controller. | RD-WMB-T |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Display for use with IQECO controller. | RD-WMB-TH |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Display for use with IQECO controller. | RD-WMB-TC |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Display for use with IQECO controller. | RD-WMB-THC |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Sensor for use with IQECO controller. | RS-WMB-T |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Sensor for use with IQECO controller. | RS-WMB-TH |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Sensor for use with IQECO controller. | RS-WMB-TC |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Sensor for use with IQECO controller. | RS-WMB-THC |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Wall mounting thermistor space temperature sensor. | TB/TS |
|
||
Specification sheet (English) Installation/startup instruction (English) |
||||
As TB/TS plus setpoint adjustment. | TB/TS/K |
|
||
Specification sheet (English) |
||||
IQECO/IQL secondary terminal cover. | ENCLS-600002 |
|
||
Specification sheet (English) |
The IQECO35 is a terminal unit controller for use with BACnet over MS/TP. It can communicate with other IQECOs over the BACnet MS/TP network, and with Trend networked devices by using an IQ4NC. It has 17 I/O channels, and can be supplied as a fixed or programmable unit, with Trend written strategies, custom strategies or no strategy.
The IQECO can be purchased either as a fully programmable or a fixed strategy model. A wide range of strategies can be downloaded to the units to provide pre-configured functionality for a host of different applications. They are classified as Entry level (E), Basic (B) or Plus (P)and can be downloaded into the respective controllers. The more popular application strategies can be ordered directly from the factory. Please see price list for details. The fixed strategy controllers will allow a degree of configuration while the programmable models allow complete flexibility. Should it be necessary to upgrade from a fixed to programmable an unlock is available.
• The programmable units allow the strategy to be modified to meet specific project requirements whereas the fixed units can only be used with a Trend supplied strategy.
• The strategy itself defines the units HVAC control method. Various Trend strategies are available and they are divided into three categories, Entry, Basic and Plus. The Entry category has less sophisticated strategies with a lower level of I/O control and the Plus category has more sophisticated strategies with the highest level of I/O control.
• Trend provide a service to supply personal strategies preloaded into the IQECO. This can significantly reduce time on site by removing the need to download the same strategy to potentially several hundred controllers.
• Units defined as No Strategy are supplied empty and can have strategies downloaded from SET.
UI | 3 |
DI | 2 |
TI | 3 |
AO | 1 |
DO | 4 |
Relay outputs | 4 |
Auxiliary output signal | 1 x 24 Vdc |
Power supply | 230 Vac |
|
|||||||
Application | Control | Programability | Additional functions | Type | Downloads | ||
---|---|---|---|---|---|---|---|
TXT | |||||||
3 speed fan | Water/Raise/Lower/2 pipe | Fixed | — | IQE35/F/BAC/3SFANWR2E/230 |
|
||
Specification sheet (English) Application manual (English) Installation/mounting instruction (English) |
|||||||
3 speed fan | Water/Raise/Lower/4 pipe | Fixed | — | IQE35/F/BAC/3SFANWR4E/230 |
|
||
Specification sheet (English) Application manual (English) Installation/mounting instruction (English) |
|||||||
3 speed fan | Water/Raise/Lower/4 pipe | Fixed | Electrical heat at 1% demand | IQE35/F/BAC/3SFANWR4EB/230 |
|
||
Specification sheet (English) Application manual (English) Installation/mounting instruction (English) |
|||||||
3 speed fan | Water/Thermic/4 pipe | Fixed | — | IQE35/F/BAC/3SFANWT4E/230 |
|
||
Specification sheet (English) Application manual (English) Installation/mounting instruction (English) |
|||||||
3 speed fan | Water/Raise/Lower/2 pipe | Programmable | — | IQE35/P/BAC/3SFANWR2E/230 |
|
||
Specification sheet (English) Application manual (English) Installation/mounting instruction (English) |
|||||||
3 speed fan | Water/Raise/Lower/4 pipe | Programmable | — | IQE35/P/BAC/3SFANWR4E/230 |
|
||
Specification sheet (English) Application manual (English) Installation/mounting instruction (English) |
|||||||
3 speed fan | Water/Raise/Lower/4 pipe | Programmable | Electrical heat at 1% demand | IQE35/P/BAC/3SFANWR4EB/230 |
|
||
Specification sheet (English) Application manual (English) Installation/mounting instruction (English) |
|||||||
3 speed fan | Water/Thermic/4 pipe | Programmable | — | IQE35/P/BAC/3SFANWT4E/230 |
|
||
Specification sheet (English) Application manual (English) Installation/mounting instruction (English) |
|||||||
— | Custom strategy | Fixed | — | IQE35/C/BAC/CUSTOM/230 |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
|||||||
— | No strategy | Fixed | — | IQE35/F/BAC/NOSTRATEGY/230 |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
|||||||
— | No strategy | Programmable | — | IQE35/P/BAC/NOSTRATEGY/230 |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
|
||||
Description | Additional Product Type | Downloads | ||
---|---|---|---|---|
TXT | ||||
Web enabled controller with no I/O points, non expandable by the I/O bus. Provides routing between MS/TP BACnet, Ethernet and Trend LAN. 100 to 240 Vac. | IQ4NC/00/230 |
|
||
Specification sheet (English) |
||||
Web enabled controller with no I/O points, non expandable by the I/O bus. Provides routing between MS/TP BACnet, Ethernet and Trend LAN. 24 Vac or 24 to 36 Vdc. | IQ4NC/00/24VAC |
|
||
Specification sheet (English) |
||||
Web enabled controller with 12 I/O points, non expandable by the I/O bus. Provides routing between MS/TP BACnet, Ethernet and Trend LAN. 100 to 240 Vac. | IQ4NC/12/230 |
|
||
Specification sheet (English) |
||||
Web enabled controller with 12 I/O points, non expandable by the I/O bus. Provides routing between MS/TP BACnet, Ethernet and Trend LAN. 24 Vac or 24 to 36 Vdc. | IQ4NC/12/24VAC |
|
||
Specification sheet (English) |
||||
Screened twisted-pair cable for MSTP network 24 AWG 305 metre. | TP/1/1/24/HF/305/600V |
|
||
Specification sheet (English) |
||||
Upgrade licence to convert a fixed strategy controller to a programmable controller. | IQE/PROG/UP |
|
— | |
Room Display for use with IQECO controller. | RD-WMB-T |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Display for use with IQECO controller. | RD-WMB-TH |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Display for use with IQECO controller. | RD-WMB-TC |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Display for use with IQECO controller. | RD-WMB-THC |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Sensor for use with IQECO controller. | RS-WMB-T |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Sensor for use with IQECO controller. | RS-WMB-TH |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Sensor for use with IQECO controller. | RS-WMB-TC |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Sensor for use with IQECO controller. | RS-WMB-THC |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Wall mounting thermistor space temperature sensor. | TB/TS |
|
||
Specification sheet (English) Installation/startup instruction (English) |
||||
As TB/TS plus setpoint adjustment. | TB/TS/K |
|
||
Specification sheet (English) |
||||
IQECO/IQL secondary terminal cover. | ENCLS-600002 |
|
||
Specification sheet (English) |
The IQECO38 is a terminal unit controller for use with BACnet over MS/TP. It can communicate with other IQECOs over the BACnet MS/TP network, and with Trend networked devices using an IQ4NC. It has 18 I/O channels, and can be supplied as a fixed or programmable unit, with Trend written strategies, custom strategies or no strategy.
The IQECO can be purchased either as a fully programmable or a fixed strategy model. A wide range of strategies can be downloaded to the units to provide pre-configured functionality for a host of different applications. They are classified as Entry level (E), Basic (B) or Plus (P)and can be downloaded into the respective controllers. The more popular application strategies can be ordered directly from the factory. Please see price list for details. The fixed strategy controllers will allow a degree of configuration while the programmable models allow complete flexibility. Should it be necessary to upgrade from a fixed to programmable an unlock is available.
• The programmable units allow the strategy to be modified to meet specific project requirements whereas the fixed units can only be used with a Trend supplied strategy.
• The strategy itself defines the units HVAC control method. Various Trend strategies are available and they are divided into three categories, Entry, Basic and Plus. The Entry category has less sophisticated strategies with a lower level of I/O control and the Plus category has more sophisticated strategies with the highest level of I/O control.
• Trend provide a service to supply personal strategies preloaded into the IQECO. This can significantly reduce time on site by removing the need to download the same strategy to potentially several hundred controllers.
• Units defined as No Strategy are supplied empty and can have strategies downloaded from SET.
UI | 4 |
DI | 2 |
TI | 3 |
AO | 4 |
DO | 4 |
Relay outputs | 1 |
Auxiliary output signal | 1 x 24 Vdc |
|
||||||
Control | Programability | Power supply | Type | Downloads | ||
---|---|---|---|---|---|---|
TXT | ||||||
Custom strategy | Custom | 24Vac | IQE38/C/BAC/Custom/24VAC |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||||
Custom strategy | Custom | 230Vac | IQE38/C/BAC/Custom/230 |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||||
No strategy | Fixed | 24Vac | IQE38/F/BAC/NOSTRATEGY/24VAC |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||||
No strategy | Fixed | 230Vac | IQE38/F/BAC/NOSTRATEGY/230 |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||||
No strategy | Programmable | 24Vac | IQE38/P/BAC/NOSTRATEGY/24VAC |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||||
No strategy | Programmable | 230Vac | IQE38/P/BAC/NOSTRATEGY/230 |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
|
||||
Description | Additional Product Type | Downloads | ||
---|---|---|---|---|
TXT | ||||
Web enabled controller with no I/O points, non expandable by the I/O bus. Provides routing between MS/TP BACnet, Ethernet and Trend LAN. 100 to 240 Vac. | IQ4NC/00/230 |
|
||
Specification sheet (English) |
||||
Web enabled controller with no I/O points, non expandable by the I/O bus. Provides routing between MS/TP BACnet, Ethernet and Trend LAN. 24 Vac or 24 to 36 Vdc. | IQ4NC/00/24VAC |
|
||
Specification sheet (English) |
||||
Web enabled controller with 12 I/O points, non expandable by the I/O bus. Provides routing between MS/TP BACnet, Ethernet and Trend LAN. 100 to 240 Vac. | IQ4NC/12/230 |
|
||
Specification sheet (English) |
||||
Web enabled controller with 12 I/O points, non expandable by the I/O bus. Provides routing between MS/TP BACnet, Ethernet and Trend LAN. 24 Vac or 24 to 36 Vdc. | IQ4NC/12/24VAC |
|
||
Specification sheet (English) |
||||
Screened twisted-pair cable for MSTP network 24 AWG 305 metre. | TP/1/1/24/HF/305/600V |
|
||
Specification sheet (English) |
||||
Upgrade licence to convert a fixed strategy controller to a programmable controller | IQE/PROG/UP |
|
— | |
Room Display for use with IQECO controller. | RD-WMB-T |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Display for use with IQECO controller. | RD-WMB-TH |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Display for use with IQECO controller. | RD-WMB-TC |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Display for use with IQECO controller. | RD-WMB-THC |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Sensor for use with IQECO controller. | RS-WMB-T |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Sensor for use with IQECO controller. | RS-WMB-TH |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Sensor for use with IQECO controller. | RS-WMB-TC |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Sensor for use with IQECO controller. | RS-WMB-THC |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Wall mounting thermistor space temperature sensor. | TB/TS |
|
||
Specification sheet (English) Installation/startup instruction (English) |
||||
As TB/TS plus setpoint adjustment. | TB/TS/K |
|
||
Specification sheet (English) |
||||
IQECO/IQL secondary terminal cover. | ENCLS-600002 |
|
||
Specification sheet (English) |
The IQECO is a terminal unit controller for use with BACnet over MS/TP. It can communicate with other IQECOs over the BACnet MS/TP network, and with IQ system networked devices by using an IQ4NC. It has an optional actuator and pressure sensor which facilitates its use as a VAV controller. It has a maximum of 12 I/O points. As a programmable unit it allow the strategy to be modified to meet specific project requirements. The strategy itself defines the units HVAC control method.
• Fully compatible with the IQ system.
• BACnet over MS/TP (WSP certified)
• Non-volatile memory, no battery required.
• I/O configurable by software only (no links)
Control | VAV 2 Stage Electric Heater |
Programability | Programmable |
AO | 2 |
DO | 4 |
Relay outputs | 2 |
Auxiliary output signal | 1 x 24Vdc |
Power supply | 24Vac |
Pressure connection | Differential pressure sensor |
|
|||||
Additional functions | UI | Type | Downloads | ||
---|---|---|---|---|---|
TXT | |||||
— | 6 | IQEVAVP/P/BAC/VAV2E/24VAC |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
|||||
Fitted Actuator | 4 | IQEVAVPA/P/BAC/VAV2E/24VAC |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
|
||||
Description | Additional Product Type | Downloads | ||
---|---|---|---|---|
TXT | ||||
Web enabled controller with no I/O points, non expandable by the I/O bus. Provides routing between MS/TP BACnet, Ethernet and Trend LAN. 100 to 240 Vac. | IQ4NC/00/230 |
|
||
Specification sheet (English) |
||||
Web enabled controller with no I/O points, non expandable by the I/O bus. Provides routing between MS/TP BACnet, Ethernet and Trend LAN. 24 Vac or 24 to 36 Vdc. | IQ4NC/00/24VAC |
|
||
Specification sheet (English) |
||||
Web enabled controller with 12 I/O points, non expandable by the I/O bus. Provides routing between MS/TP BACnet, Ethernet and Trend LAN. 100 to 240 Vac. | IQ4NC/12/230 |
|
||
Specification sheet (English) |
||||
Web enabled controller with 12 I/O points, non expandable by the I/O bus. Provides routing between MS/TP BACnet, Ethernet and Trend LAN. 24 Vac or 24 to 36 Vdc. | IQ4NC/12/24VAC |
|
||
Specification sheet (English) |
||||
Screened twisted-pair cable for MSTP network 24 AWG 305 metre. | TP/1/1/24/HF/305/600V |
|
||
Specification sheet (English) |
||||
Upgrade licence to convert a fixed strategy controller to a programmable controller | IQE/PROG/UP |
|
— | |
Room Display for use with IQECO controller with local sensor temperature sensor, setpoint control | RD-WMB-T |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Display for use with IQECO controller with local sensor temperature sensor, setpoint control, occupation override, and occupation status display |
RD-WMB-TH |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Display for use with IQECO controller with local sensor temperature sensor, setpoint control, occupation override, and occupation status display |
RD-WMB-TC |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Display for use with IQECO controller with local sensor temperature sensor, setpoint control, occupation override, and occupation status display |
RD-WMB-THC |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Sensor for use with IQECO controller with local sensor temperature sensor, setpoint control, occupation override, and occupation status display |
RS-WMB-T |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Sensor for use with IQECO controller with local sensor temperature sensor, setpoint control, occupation override, and occupation status display |
RS-WMB-TH |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Sensor for use with IQECO controller with local sensor temperature sensor, setpoint control, occupation override, and occupation status display |
RS-WMB-TC |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Room Sensor for use with IQECO controller with local sensor temperature sensor, setpoint control, occupation override, and occupation status display |
RS-WMB-THC |
|
||
Specification sheet (English) Installation/mounting instruction (English) |
||||
Wall mounting thermistor space temperature sensor. | TB/TS |
|
||
Specification sheet (English) Installation/startup instruction (English) |
With our innovative approach in product design and advanced production technical capabilities for building environments of any size